"How many GPU servers fit in a rack?" sounds simple, but the answer is rarely the number of empty U. With modern GPU servers, power and heat run out long before space does. This article gives a quick method and a reference table.
Five limits of a rack
- Power: the combined maximum draw must not exceed the rack's committed power.
- Cooling: every kW becomes heat; conventional air cooling has limits, high densities need liquid.
- Space (U): 42U or 47U racks, minus room for switches and patch panels.
- Weight: a DGX B200 weighs up to about 142 kg; check rack and floor load ratings.
- Cabling and network: 8-GPU servers have many high-speed ports; plan cable paths and switches.
Specs of two common systems
| System | Max power | Height | Max weight |
|---|---|---|---|
| NVIDIA DGX H100 | 10.2 kW | 8U | 130.45 kg |
| NVIDIA DGX B200 | ~14.3 kW | 10U | 142.4 kg |
OEM HGX servers (Supermicro, Dell, Lenovo…) vary by configuration; always use the nameplate power or the datasheet of the exact model.
Quick sizing table by rack power
Method: rack power divided by each server's max power, rounded down, capped at 40U usable (a 42U rack minus about 2U for patch panel and management switch). GPU fabric switches are assumed to sit in a separate network rack.
| Rack power | DGX H100 | DGX B200 | Notes |
|---|---|---|---|
| 10 kW | 0 | 0 | |
| 15 kW | 1 | 1 | |
| 20 kW | 1 | 1 | |
| 30 kW | 2 | 2 | |
| 40 kW | 3 | 2 | Needs high-density cooling (rear-door / liquid) |
| 60 kW | 5 | 4 | Needs high-density cooling (rear-door / liquid) |
Why not fill the rack?
Four DGX B200s take only 40U but need roughly 60 kW per rack, which already pushes the limits of air-cooled racks in many data centers. Rack-scale systems such as GB200 NVL72 are rated around 120 kW and require liquid cooling. On air-cooled infrastructure it is usually better to spread servers across more racks.
Applying this to FPT Data Center plans
- 4–6 kW/rack: small PCIe GPU servers, inference boxes, storage and networking.
- 6–10 kW/rack: some PCIe or 4-GPU configurations; new 8-GPU servers usually exceed this.
- Over 10 kW/rack (expandable): suited to 8-GPU servers; servers per rack follow the table above.
See the detailed method in how to estimate GPU rack power and the cost side in GPU colocation pricing explained.
Send me your server models and I will work out the number of racks, power and cooling approach at FPT Data Center.
Frequently asked questions
How many DGX B200 servers fit in a 42U rack?
Space allows four (10U each), but that needs about 60 kW. At 30 kW per rack, plan for two; at 15 kW, one.
Should I plan by maximum or average power?
Plan by maximum (nameplate) power so you never exceed the committed rack power when GPUs run at full load during training.
When is liquid cooling needed?
Once rack density reaches several tens of kW. Rack-scale systems such as GB200 NVL72 (around 120 kW) require liquid cooling.