How many GPU servers fit in one rack? Sizing by power, cooling and space

QD Đỗ Quốc Duy · Data Center & Digital Transformation Consultant, FPT Telecom International
Key points: How many GPU servers fit in one rack? Sizing by power, cooling and space
Key points: How many GPU servers fit in one rack? Sizing by power, cooling and space

"How many GPU servers fit in a rack?" sounds simple, but the answer is rarely the number of empty U. With modern GPU servers, power and heat run out long before space does. This article gives a quick method and a reference table.

Five limits of a rack

  1. Power: the combined maximum draw must not exceed the rack's committed power.
  2. Cooling: every kW becomes heat; conventional air cooling has limits, high densities need liquid.
  3. Space (U): 42U or 47U racks, minus room for switches and patch panels.
  4. Weight: a DGX B200 weighs up to about 142 kg; check rack and floor load ratings.
  5. Cabling and network: 8-GPU servers have many high-speed ports; plan cable paths and switches.

Specs of two common systems

SystemMax powerHeightMax weight
NVIDIA DGX H10010.2 kW8U130.45 kg
NVIDIA DGX B200~14.3 kW10U142.4 kg

OEM HGX servers (Supermicro, Dell, Lenovo…) vary by configuration; always use the nameplate power or the datasheet of the exact model.

Quick sizing table by rack power

Method: rack power divided by each server's max power, rounded down, capped at 40U usable (a 42U rack minus about 2U for patch panel and management switch). GPU fabric switches are assumed to sit in a separate network rack.

Rack powerDGX H100DGX B200Notes
10 kW00
15 kW11
20 kW11
30 kW22
40 kW32Needs high-density cooling (rear-door / liquid)
60 kW54Needs high-density cooling (rear-door / liquid)
Diagram of a 42U, 30 kW rack holding two 10U DGX B200 servers, a patch panel and management switch, with A and B PDUs on both sides
Example 42U rack at 30 kW: two DGX B200 servers (about 28.6 kW max), with space left for airflow.

Why not fill the rack?

Four DGX B200s take only 40U but need roughly 60 kW per rack, which already pushes the limits of air-cooled racks in many data centers. Rack-scale systems such as GB200 NVL72 are rated around 120 kW and require liquid cooling. On air-cooled infrastructure it is usually better to spread servers across more racks.

Applying this to FPT Data Center plans

See the detailed method in how to estimate GPU rack power and the cost side in GPU colocation pricing explained.

Send me your server models and I will work out the number of racks, power and cooling approach at FPT Data Center.

Frequently asked questions

How many DGX B200 servers fit in a 42U rack?

Space allows four (10U each), but that needs about 60 kW. At 30 kW per rack, plan for two; at 15 kW, one.

Should I plan by maximum or average power?

Plan by maximum (nameplate) power so you never exceed the committed rack power when GPUs run at full load during training.

When is liquid cooling needed?

Once rack density reaches several tens of kW. Rack-scale systems such as GB200 NVL72 (around 120 kW) require liquid cooling.